G1: 100 MVA, 25 kV, X1-X2-0.20, X0-0.05 per unit, Zng-j0.03
G2: 100 MVA, 13.8 kV, X1-X2-0.20, X0=0.05 per unit, Zng-j0.03
T1: 100 MVA, 25 kV Y/230 kV Y, X-0.05 per unit
T2: 100 MVA, 13.8 kV A/230 kV Y, X-0.05 per unit
Line 1-2: 100 MVA, 230 kV, X1=X2-0.1, X0-0.3
Line 1-3: 100 MVA, 230 kV, X1-X2-0.1, X0-0.3
Line 2-3: 100 MVA, 230 kV, X1=X2-0.1, X0-0.3
Using a 100 MVA, 230 kV base for the transmission lines, draw the per-unit sequence networks
and reduce them to their Thevenin equivalents, "looking in" at bus 3. Neglect transformer
phase shifts. Compute the fault currents for a bolted three-phase fault at bus 3.
Fig: 1