600 kVA, S2=300 kVA, and S3 = 500 kVA
(a) If the Kdrop factor of the feeder is 0.000147 % drop/kVA-km,
calculate the total percent drop from N1 to N3.
(b) If the total percentage drop from N2 to N4 is 2.1%, calculate
the Kdrop factor of the feeder.
(c) A capacitor of 300 kVAr is connected at the node N4. If the
voltage drop is improved from 2.8% to 1.5% due to the capacitor for the
given loading, calculate the Krise factor (%rise / kVAr-km) of the feeder.
Fig: 1