7.12 Equipment ratings for the four-bus power system shown in

Question
7.12 Equipment ratings for the four-bus power system shown in Figure 7.12 are as follows:

Generator Gl:

Generator G2:

Generator G3:

500 MVA, 13.8 kV, X" = 0.20 per unit

750 MVA, 18 kV, X"=0.18 per unit

1000 MVA, 20 kV, X"=0.17 per unit

500 MVA, 13.8 A/500. Y kV, X = 0.12 per unit

750 MVA, 18 A/500 Y kV, X = 0.10 per unit

1000 MVA, 20 A/500 Y kV, X = 0.10 per unit

7.12

558:1.-11:8

150 n

¡50 n

ot

Transformer TI:

Transformer T2:

Transformer T3:

Each 500-kV line: X₁ = 50 52

A three-phase short circuit occurs at bus 1, where the prefault voltage is 525 kV.

Prefault load current is neglected. Draw the positive-sequence reactance diagram in

7.13,

, 7.26

G1

T1

AY

T2

G2

150 n

T3

of 3€

YA

G3

PROBLEMS 387

per-unit on a 1000-MVA, 20-kV base in the zone of generator G3. Determine (a) the

Thévenin reactance in per-unit at the fault, (b) the subtransient fault current in per-

unit and in kA rms, and (c) contributions to the fault current from generator G1 and

from line 1-2.