8. Refrigerant R-134a enters the condenser (heat exchanger for rejection) of a heat pump at 700
kPa and 40 °C and a mass flow rate of 0.02 kg/s. It leaves the condenser as saturated liquid at the
same pressure. The compressor consumer 1.2 kW power. Determine (a) the COP of the heat
pump, and (b) the rate at which heat transferred from the outside air. (Watch "Carnot Flow-