A 20.5-KV 16-MVA 60-Hz Y-connected synchronous generator has a
synchronous reactance of 10 per phase and an armature resistance
of 10 per phase. The generator supplies 12-MVA load with 0.9 power
factor lagging at 20.5-kV. Neglecting the impedance of the lines
between the terminals of the generator and the load, find the
following:
(a) The value of EA (per phase).
(b) The efficiency of the generator. [efficiency =100% *(Pout/Pin)]