Two thermocouples are placed in an air stream whose temperature is varying
sinusoidally. The temperature responses of each thermocouple are recorded
for a range of frequencies, with the phase angle between the two
measurements tabulated below. The standard thermocouple is known to have
first-order dynamics with a time constant of 0.15 minutes when operating in
air. Show the unknown thermocouple also displays first order behavior and
determine its time constant.
After approximately 30 seconds the standard themocouple shows a sinusoidal
variation in air temperature between 96 and 104 degrees Celcius, at a rate of
two cycles per minute. What error will the standard thermocouple report in
this instance if left to measure the air temperature indefinitely?
CHEM ENG 4050: Advanced Chemical Engineering
Advanced Control
Table 1. Thermocouple phase difference for Question 4.
Frequency
(cycles/min)
0.05
0.1
0.2
0.4
0.8
1.0
2.0
4.0
Phase Difference
(deg)
4.5
8.7
16.0
24.5
26.5
25.0
16.7
9.2
Fig: 1